E. Gartland & Associates, LLC

E. Gartland Home     Refrigerant R-407A     About Us     Contact Us     News      
R-407A

In use since the 1990's the R-407 series refrigerants are the best match for replacing R-22 in refrigeration and air-conditioning applications.  Case studies show 5%-10% energy savings over other alternatives.


 Application
IPCC4 GWP Value
Comments
R-407A Low & Medium temperature refrigeration
2,107
 Great capacity & energy match for R-22
provides excellent heat reclaim
54% lower GWP than R-404A
Must use synthetic oils
R-407C
Medium temperature refrigeration
air-conditioning
 1,774 Loses capacity at low evap temps
Great HVAC retrofit product
Must use synthetic oils
R-134aMedium temperature refrigeration
auto air-conditioning
1,430
 Must use synthetic oils


Product details

R407A is a blend of R-32 (CH2F2), R-125 (CH2CF3), and R-134a (CF3CH2F) in a 20/40/40 ratio by mass.

Property British Units S.I. Units
Bubble Point -49.0 (°F @ 14.7psia) -45.3 (°C @ 1bar)
Dew Point -37.5 (°F @ 14.7psia) -38.9 (°C @ 1bar)
Evaporator Glide 7.7 (°F @ 14.7psia) 4.3 (°C @ 1bar)
Bubble Point Pressure 163.5 (psia @ 70°F) 12.5 (bara @ 25°C)
Critical Temperature 180.1 (°F) 82.3 (°C)
Latent Heat Vaporization 82.6 (Btu/lb @ 70°F) 186.5 (kJ/kg @ 25°C)
Coeff. Vol. Therm. Exp. 0.0020 (°F -1 40-80°F) 0.0035 (K-1 0-20°C)
Saturated Vapor Density 0.305 (lb/cuft @ nBpt) 4.82 (kg/m3 @ nBpt)

 PT Chart for all productsThermodynamic Properties
 
 Supermarket Case Study
Supermarket Retrofit 
Frozen Food Store Retrofit


R407C
is a blend of R32 (CH2F2), R125 (CH2CF3), and R134a (CF3CH2F) in a 23/25/52 ratio by mass.

Property British Units S.I. Units
Bubble Point -47.2 (°F @14.7psia) -44.0 (°C @1 atm)
Dew Point -34.2(°F @14.7psia) -36.8 (°C @1 atm)
Evaporator Glide 8.6 (°F @14.7psia) 4.8 (°C @1 atm)
Bubble Point Pressure 155.7 (psia@ 70°F) 11.9 (bara @ 25°C)
Critical Temperature 186.9 (°F) 86.0 (°C)
Latent Heat Vaporization 82.8 (Btu/lb@70°F) 188.25 (kJ/kg @25°C)
Coeff. Vol. Therm. Exp. 0.0019 (°F-140-80°F) 0.0037 (K-10-20°C)
Saturated Vapor Density 0.286 (lb/cuft @nBpt)> 4.58 (kg/m³@nBpt)



Emerson Announces Copeland Discus® Compressors Approval With R-407A and R-407C Refrigerants Bulletin 8-10